Main Features:
2-ports(RJ-45) Ethernet 10/100 Based-T Comm.
Daisy chain connection with auto-bypass protection
Support Modbus/TCP,TCP/IP,UDP,ICMP,ARP
Support Automatic DIO Sync.(peer-to-peer).
DO Auto-Off Time Mode.
Support 8 Isolated with open drain (P-MOSFET), 750mA/channel.
Support 5 Isolated differential digital input
Fully Photo-Isolation 3750Vrms
Protocol: ASCII Format & Modbus TCP
Specifications:
Interface: |
|
Communication |
2-port(RJ45)
Ethernet 10/100 Based-T
comm, Daisy chain connection with auto-bypass
protection. |
|
Protocol |
Modbus/TCP,
TCP/IP, UDP, ICMP and ARP |
|
Led indication |
Led for power
and Ethernet link status |
|
Isolation Digital Input: |
|
Input channels |
5 (DI0~4) |
|
Input type: |
differential
●
logic level 0 (active) : +5V to +30VDC max
●
logic level 1 (inactive): +0V to +1VDC max
Logic level status can be inversed via ASCII/Modbus
command |
|
Input Impedance |
2K ohm |
|
Counter Input |
300Hz counter
input (32-bit+1-bit overflow) |
|
Optical
Isolation Voltage |
3750Vrms |
|
Isolation Digital Output: |
|
Output channels |
8 (DO0~7) |
|
Output type: |
Isolated open
drain (P-MOSFET)
Load voltage: +10V to +30VDC
Load current: 750mA/ channel Max. (With short-circuit
protection)
Logic level status can be inversed via ASCII/Modbus
command |
|
Pulse output |
Each channel
supports 300Hz pulse output |
|
Optical
Isolation Voltage |
3750Vrms |
|
Power requirement: |
|
Consumption |
3.6W (Typical) |
|
Power input |
10~30VDC |
|
Operating
temperature: |
-10 ~ 70° C
(14 ~ 158° F) |
|
Operating
temperature: |
-25 ~ 85 °C
(13 ~ 185 °F) |
|
Humidity |
5~95% RH,
non-condensing |
|
Features:
Daisy Chain Networking and Auto-Bypass Protection
Daisy chain connectivity offers flexible cabling and space
saving capabilities. With Ethernet auto-bypass function
supported, it prevents accidental power failure if one of the
module’s unexpectedly shuts down.
Automatic DIO Synchronization (peer-to peer)
EX9200-MTCP series module also provide a Automatic DIO Synchronization
function. With peer-to-peer networking, users can define the
mapping between a Pair of EX9200-MTCP series modules so that
input values will be directly transferred to output channels. A
single digital output channel(Local/ Remote device) is
activated(1/0 or toggle)dependent on the digital input channels
state data pattern. When the specified DI channels state data
pattern changed from “Match” to “Not match” the corresponding DO
well be set to active(1 or 0).
|